Other

We have named the most common industrial sectors which regularly need our starter. Naturally, the starter can be also implemented in any other sector. The following machines are usually operated, for which we can configure our starters:

Centrifugal pumps

Normally centrifugal pumps do not have an especially high moment of inertia. It is usually located in the range of app. 20-50% of the moment of inertia of the driving electric motor. Therefore, pump drives can be started with a relatively short start time of 5-15 seconds. The torque speed curves of nearly all centrifugal pumps have a quadratic shape (counter torque). The pump should be started with closed discharge valve, which reduces the power consumption of the pump during the start. The counter torque of the pump will be minmized which results in a further reduction of the start current. Start currents (Ia/In) during the start of centrifugal pumps are ususally in the range of app. 1,5-3 times of the motor start current at direct on line (IDOL/In). 

 

In the following chart a typical pump characteristics is shown:

Diagramm 01

The corresponding power consumption looks like this:            

Diagramm 02

 

 

Therefore the power consumption of the pump is 30 % of its maximum power consumption, if the pump is started with a closed discharge valve. (flow rate Q=0). In the following torque chart the torque speed curve of the pump has its usual quadratic shape. It ends (speed n/nn = 1) at a torque requirement of 30 % (this corresponds to the power consumption of the pump).

 

Start calculation

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.500   rpm
moments of inertia            
  motor   JM   80   kgm2
  driven machine   JL   50   kgm2
start voltage   Us   0,61   x Un
start time   ts   9   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 61 % of the rated voltage, in this example (Us/Un = 0,61). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,61 × 0,91)2 = 0,31 (F is a factor dependent on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 80 + 50 kgm2 = 120 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,61 × 5 × 0,91 = 2,8 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,61 × 2,8 = 1,7 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,8 × In

For that reason these starting methods create a higher mains voltage drop.

Piston pumps

Normally piston pumps do not have an especially high moment of inertia with reference to the motor speed. It is usually located in the range of app. 10 - 40% of the moment of inertia of the driving motor. Therefore, piston pump drives can be started with a relatively shot start time of app. 5-15 seconds. Piston pumps can be started nearly without load by pressure release. This is achieved by opening valves and results in a very low counter torque which greatly reduces the start current of the piston pump. Start currents (Ia/In) during the start of piston pumps are ususally in the range of app. 1 - 2 times of the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.000   rpm
moments of inertia            
  motor   JM   150   kgm2
  piston pump   JL   35   kgm2
start voltage   Us   0,47   x Un
start time   ts   9   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 47 % of the rated voltage, in this example (Us/Un = 0,47). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,47 × 0,9)2 = 0,18 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 150 + 35 kgm2 = 185 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,47 × 5 × 0,9 = 2,1 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,47 × 2,1 = 1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,1 × In

For that reason these starting methods create a higher mains voltage drop.

Other pumps

Pumps exist in a variety of different designs and types. For the most common ones (centrifugal and piston pump) we have prepared detailled information for the start procedure. Needless to say, our starter can also be used for further pump types. We will gladly provide you with an offer and technical support.

 

Turbo compressors

The moment of inertia of a turbo compressor normally ranges between 2 to 6 times the moment of inertia of the driving motor. Most of the compressor drives start with a starting time between app. 20 to 50 seconds. The torque speed curves (counter torque) of nearly all turbo compressors have a quadratic shape. They can be started with reduced load by regulating vanes and/or blades. By this a lower counter torque is reached which can further reduce the start current. Normal start currents for turbo compressors (Ia/In) are in the range of app. 1,5 - 2,5 times the motor rated current (In). Below you will find a characteristic example for a calculation. When starting a turbo compressor one has to observe that the critical speed will be run through fast enough to avoid mechanical vibration problems.

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   1.500   rpm
moments of inertia            
  motor   JM   80   kgm2
  compressor   JL   300   kgm2
start voltage   Us   0,57   × Un
start time   ts   30   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 57 % of the rated voltage, in this example (Us/Un = 0,57). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,57 × 0,91)2 = 0,27 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 80 + 300 kgm2 = 380 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,57 × 5 × 0,91 = 2,6 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,57 × 2,6 = 1,5 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,6 × In

For that reason these starting methods create a higher mains voltage drop.

Screw compressors

Amongst others screw compressors are applied as refrigeration compressors for air condition (chiller). The moment of inertia of a screw compressor is significantly lower that the moment of inertia of the driving motor. Most of the screw compressors will start with start times between app. 10 to 20 seconds. They can be started with reduced load. This results in a lower counter torque which can further reduce the start current. Normal start currents for screw compressors (Ia/In) range from app. 1 -3 times the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   3.000   rpm
moments of inertia            
  motor   JM   45   kgm2
  compressor   JL   8   kgm2
start voltage   Us   0,63   × Un
start time   ts   17   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 63 % of the rated voltage, in this example (Us/Un = 0,63). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,63 × 0,91)2 = 0,33 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 45 + 8 kgm2 = 53 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,63 × 5 × 0,91 = 2,9 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,63 × 2,9 = 1,8 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,9 × In

For that reason these starting methods create a higher mains voltage drop.

Piston compressors

Normally piston compressors do not have an especially high moment of inertia with reference to the motor speed. It is usually located in the range of app. 10 - 40% of the moment of inertia of the driving motor. Therefore, piston compressor drives can be started with a relatively short start time of app. 5-15 seconds. Piston compressors can be started nearly without load by pressure release. This is achieved by opening valves and results in a very low counter torque which greatly reduces the start current of the piston compressor. Start currents (Ia/In) during the start of piston compressors are ususally in the range of app. 1 - 2 times of the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.000   rpm
moments of inertia            
  motor   JM   150   kgm2
  piston compressor   JL   35   kgm2
start voltage   Us   0,47   x Un
start time   ts   9   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 47 % of the rated voltage, in this example (Us/Un = 0,47). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,47 × 0,9)2 = 0,18 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 150 + 35 kgm2 = 185 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,47 × 5 × 0,9 = 2,1 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,47 × 2,1 = 1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,1 × In

For that reason these starting methods create a higher mains voltage drop.

Other compressors

Compressors exist in a variety of different designs and types. For the most common ones (turbo, screw and piston) we have prepared detailled information for the start procedure. Needless to say, our starter can also be used for further compressor types. We will gladly provide you with an offer and technical support.

 

Fans / Blowers

Fans (sometimes also called blowers) usually have a very high moment of inertia; it is often many times higher than the moment of inertia of the driving motor. Therefore most of the fan drives start with a very long start time of up to app. 100 seconds. The torque speed curves (counter torque) of nearly all fans have a quadratic shape. Most fans can be started with reduced load by adjusting the blades. This adjustment provides a lower counter torque which results in a lower start current. Normal start currents for fans (Ia/In) are in the range of app. 1,5 - 3  times the motor rated current (In). Below you will find a characteristic example for a calculation.  Due to the possibly high moment of inertia of the fan and the resulting very long start time the moment of inertia  J [kgm2] (which can be estimated in the first step) should be present for an offer. 

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.000   rpm
moments of inertia            
  motor   JM   150   kgm2
  fan   JL   2500   kgm2
start voltage   Us   0,61   x Un
start time   ts   80   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 61% of the rated voltage, in this example (Us/Un = 0,61). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,61 × 0,91)2 = 0,31 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 150 + 2.500 kgm2 = 2.650 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,61 × 5 × 0,91 = 2,8 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,61 × 2,8 = 1,7 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,8 × In

For that reason these starting methods create a higher mains voltage drop.

Bow and stern thrusters

Bow and stern thrusters ususally have low moments of inertia; they are normally slightly smaller than the moment of inertia of the driving motors. Therefore most thrusters start with a relatively short start time. Their average start times range from app. 5 to 10 seconds. The torque speed curves of nearly all thrusters have a quadratic shape. Many thrusters can be started with reduced load by adjusting the pitch control to zero pitch. This results in a very low counter torque of the thruster therewith extensively reducing the start current. The normal start currents of thrusters (Ia/In) are in the range of app. 1 - 2 times the motor rated current (In). Below you will find a characteristic example for a calculation.
 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.000   rpm
moments of inertia            
  motor   JM   150   kgm2
  thruster   JL   70   kgm2
start voltage   Us   0,5   x Un
start time   ts   9   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 50% of the rated voltage, in this example (Us/Un =0,5). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,5 × 0,9)2 = 0,2 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 150 + 70 kgm2 = 220 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,5 × 5 × 0,9 = 2,25 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,5 × 2,25 = 1,1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,25 × In

For that reason these starting methods create a higher mains voltage drop.

Main propulsion of vessels

The main propulsion of a vessel normally has a low moment of inertia; in general, it is lower than the moment of inertia of the driving motor. Therefore most main propulsions start with a short start time. Usual start times range between app. 5 to 10 seconds. The torque speed curves of nearly all vessel propulsions have a quadratic shape (counter torque). Only main propultion systems, which can minimize the counter torque by pitch control, gain an effective reduction of the start current when using a starter. In case that pitch control is possible, normal start currents for main propulsions (Ia/In) are in the range of app. 1-2 times the motor rated current(In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   4.000   kW
rated voltage   Un   6.000   V
motor rated current   In   500   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   1.000   rpm
moments of inertia            
  motor   JM   300   kgm2
  propeller   JL   140   kgm2
start voltage   Us   0,5   × Un
start time   ts   9   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 50 % of the rated voltage, in this example (Us/Un = 0,5). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,5 × 0,9)2 = 0,2 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 300 + 140 kgm2 = 440 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,5 × 5 × 0,9 = 2,25 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,5 × 2,25 = 1,1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,25 × In

For that reason these starting methods create a higher mains voltage drop.

Rotating converters

Rotating converters are a combination of an electrical motor and a generator with their shafts tightly coupled. Both machines run with a speed of 600 rpm; the motor is a 10 pole machine, the generator a 12 pole machine (or vice versa). The converter is aiming to change the net frequency from 50 to 60 Hz (or vice versa). The converter can for instance be used to provide power supply to foreign vessels in a harbour. For the start calculation the moment of inertia of both machines must be taken into account. The start time of rotating converter normally ranges between app. 10 - 20 seconds. They can be started nearly without load, because the generator will only be loaded after the start; only a very low counter torque due to friction has to be considered which greatly reduces the start current. Normal start current for converters (Ia/In) are in the range of app. 1 - 1,5 times the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   600   rpm
moments of inertia            
  motor   JM   450   kgm2
  rotating converter   JL   500   kgm2
start voltage   Us   0,47   × Un
start time   ts   15   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 47 % of the rated voltage, in this example (Us/Un = 0,47). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,47 × 0,9)2 = 0,18 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 450 + 500 kgm2 = 950 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,47 × 5 × 0,9 = 2,1 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,47 × 2,1 = 1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,1 × In

For that reason these starting methods create a higher mains voltage drop.

Controlable couplings (f.ex. hydraulic)

If a controllable coupling (f.ex. hydraulic) is located between the electrical motor and the driven load, the characteristic of the load does not influence the start process at all. We only need to consider the moment of inertia of the motor and the very small moment of inertia of the coupling half at the motor side for the start calculation. This results in a short start time of app. 5-15 seconds. The start will be carried out almost without load. The coupling generates only a very small counter torque. Therefore the start current can be greatly reduced. Typical start currents (Ia/In) for the start of controllable coupled drives are in the range of app. 1-1,5 times of the motor rated current (In). Below you will find a characteristic example of a calculation:

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   1.500   rpm
moments of inertia            
  motor   JM   80   kgm2
  coupling   JL   5   kgm2
start voltage   Us   0,47   × Un
start time   ts   8   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 47 % of the rated voltage, in this example (Us/Un = 0,47). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,47 × 0,9)2 = 0,18 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 80 + 5 kgm2 = 85 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,47 × 5 × 0,9 = 2,1 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,47 × 2,1 = 1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,1 × In

For that reason these starting methods create a higher mains voltage drop.

Extruders

Extruder are (mostly heated) screw conveyors and are mainly used in the plastic processing industry and in the food sector. Sometimes an extruder is also called mixer. The extruder usually has a low moment of inertia; it is normally lower than the moment of inertia of the driving motor. Most of the extruder drives start with a start time between app. 10 and 20 seconds as well as in empty condition (no material in the screw). The empty condition provides a lower counter torque and therefore a greater reduction of the start current. However, a certain counter torque due to residues and crustifications still remaining in the screw has to be taken into consideration. The normal start currents of extruders (Ia/In) are in the range of app. 2-3,5 times the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   4.000   kW
rated voltage   Un   6.000   V
motor rated current   In   500   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.500   rpm
moments of inertia            
  motor   JM   200   kgm2
  extruder   JL   120   kgm2
start voltage   Us   0,69   x Un
start time   ts   15   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 69% of the rated voltage, in this example (Us/Un =0,69). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,69 × 0,92)2 = 0,63 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 200 + 120 kgm2 = 320 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,69 × 5 × 0,92 = 3,2 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,69 × 3,2 = 2,2 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 3,2 × In

For that reason these starting methods create a higher mains voltage drop.

Shredders

Shredders usually feature controllable hydraulic couplings between the electric motor and the mill. Therefore, the characteristics of the shredder does not influence the start process. We only need to consider the moment of inertia of the motor and the very small moment of inertia of the coupling half at the motor side for the start calculation. This results in a very short start time of app. 5-15 seconds. The start will be carried out almost without load.The coupling generates only a very small counter torque. Therefore the start current can be greatly reduced. Typical start currents (Ia/In) for the start of a shredder range at app. 1 - 1,5 times of the motor start current at direct on line (IDOL/In). Below you will find a characteristic example of a calculation:

 

motor rated power   Pn   2.000   kW
rated voltage   Un   6.000   V
motor rated current   In   250   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   1.500   rpm
moments of inertia            
  motor   JM   80   kgm2
  coupling   JL   5   kgm2
start voltage   Us   0,47   × Un
start time   ts   8   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 47 % of the rated voltage, in this example (Us/Un = 0,47). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,47 × 0,9)2 = 0,18 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 80 + 5 kgm2 = 85 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,47 × 5 × 0,9 = 2,1 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,47 × 2,1 = 1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,1 × In

For that reason these starting methods create a higher mains voltage drop.

Mills

Mills exist in a variety of different designs and types. We have prepared detailled information for the start procedure of a shredder. Needless to say, our starter can also be used for further mill types, if the start torque requirement of the mill is not too high. High moments of inertia and therefore long start times do not pose a problem for our starter. If a controlable (f. ex. hydraulic) coupling is mounted between mill and motor, the mill can be started with a very low start current (Ia/In) in the range of app. 1-2 times of the motor start current at direct on line (IDOL/In). We will gladly provide you with an offer and technical support.

 

Refiner

Refiners are used to shred (grind) fibers (f.ex. pulp or waste paper) in the wood and paper industry. Refiners normally have a relatively high moment of inertia, which is usually higher than the moment of inertia of the driving motor. Most of the refiners start with a starting time of app. 30 to 50 seconds. They are started in empty condition (no fibers in the refiner). This results in a very low counter torque of the refiner, therefore an extensive reduction of the start current is possible. Normal start currents for refiners (Ia/In) are in the range of app. 1 - 2,5 times the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   4.000   kW
rated voltage   Un   6.000   V
motor rated current   In   500   A
motor start current DOL   Ia   5   × In
motor rated speed (synchronous)   nn   1.500   rpm
moments of inertia            
  motor   JM   200   kgm2
  refiner   JL   760   kgm2
start voltage   Us   0,5   × Un
start time   ts   40   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 50 % of the rated voltage, in this example (Us/Un = 0,5). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,5 × 0,9)2 = 0,2 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 200 + 760 kgm2 = 960 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,5 × 5 × 0,9 = 2,25 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,5 × 2,25 = 1,1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,25 × In

For that reason these starting methods create a higher mains voltage drop.

Hackers

Hackers are used to shred wood in the wood/paper industry. They are applied for example in the chipboard, pelletizing, pulp and paper industry. A hackers produces chips from wood (f.ex. logs) using a rotor assembled with knifes. Hackers have a high moment of inertia due to their massive execution. It is multiple times higher than the moment of inertia of the driving motor. Therefore hacker drives start with a very long starting time between app. 50 and 120 seconds. Hackers are started in empty condition (no logs in the machine). This results in a very low counter torque and therefore in an extensive reduction of the start current. Normal start currents for hackers (Ia/In) are in the range app. 1 - 2 times the motor rated current (In). Below you will find a characteristic example for a calculation.

 

motor rated power   Pn   1.500   kW
rated voltage   Un   6.000   V
motor rated current   In   190   A
motor start current DOL   Ia   5   x In
motor rated speed (synchronous)   nn   1.000   rpm
moments of inertia            
  motor   JM   110   kgm2
  hacker   JL   1.500   kgm2
start voltage   Us   0,47   x Un
start time   ts   100   s
graph start time
 


Torque

graph torque

The starter starts the motor with reduced voltage, 47% of the rated voltage, in this example (Us/Un = 0,47). The torque speed curve of the motor will be reduced by the factor Ts/TDOL = (Us/Un × F)2.
Ts/TDOL = (0,47 × 0,9)2 = 0,18 (F is a factor depending on the motor). The torque of the motor must always be higher than the counter torque. The start voltage Us/Un has been determined accordingly. The difference between the reduced motor torque Ts and the counter torque is the acceleration torque Ta.

 

Start time

The start time ts is calculated from the acceleration torque Ta and the total moment of inertia J = JM + JL = 110 + 1.500 kgm2 = 1.610 kgm2.

formel anlaufzeit

 

Current

graph current

The motor current is IMot = Us/Un × IDOL × F = 0,47 × 5 × 0,9 = 2,1 × In

Mains start current:

A transformer has the same power at primary and secondary, which leads to the fact that the products of current and voltage are the same.

Un × Is = Us/Un × Imot => Is = Us/Un × IMot / Un

Is= 0,47 × 2,1 = 1 × In

The mains start current is therefore much lower than the motor start current.

For other start methods (electronic soft starter, starting reactor etc.) the following is valid: The mains current equals the motor current:
Is = IMot = 2,1 × In

For that reason these starting methods create a higher mains voltage drop.

Other machines

Machines driven by electric motors exist in a variety of different designs and types. For the most common ones we have prepared detailled information for the start procedure. Needless to say, our starter can also be used for further types of machines. We will gladly provide you with an offer and technical support.

 

Rufen Sie uns an!

Any questions?

Do you need support to start your drives? We are here to help. Please contact us.

0049 273565753-80
start@start-ing.de